Notice for Fire Norms Compliance in Management Platform
 
Some countries have specific requirements for how the user interface of a fire protection system appears and functions. In the United States, this set of requirements is defined by the Underwriters Laboratories (UL) in the UL 864 specifications. In Canada, the relevant norms are the Underwriters Laboratories of Canada ULC 527-11.
 
 
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864/ULC S527, certain programming features or options must be limited to specific values or not used at all as indicated in the following tables.
 
 
 
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product is not UL-listed for Security applications.
 
 
 
For Mass Notification System application, the following security levels apply:
Communication Security
Level 1
Utilize an Independent Dedicated Network
Stored Data Security
Level 0
Stored Data Security not employed
Access Control Security
Level 1
Password up to 1000 combinations and timeout feature employed
Physical Security
Level 1
Utilize a key to access equipment HW controls
Audit Control
Not provided
 
Desigo CC must be installed in a secured location for manned operation.
 
 
General System Limits
System Configuration
System Component
Permitted in UL 864,2572 / ULC S526,S527? (Y/N)
Possible Settings
Settings Permitted in UL 864,2572 / ULC S526,S527
System dimensions
Distributed systems (interconnected local systems)
Yes
3
3
Server stations
Yes
1
1
FEP stations
Yes
5
5
Web Server stations
Yes
1
1
Installed Clients
Yes
10
7
Web Clients
Yes
40
20 (for view only)
Windows App Clients
No
40
None
Mobile Clients
Yes
10
10 (for view only)
NOTE: When the Mass Notification System ( MNS) is installed within the Life Safety Network, wireless connection is not allowed.
SNMP networks per SNMP Driver
Yes
5
5
Physical Objects (fire detectors, manual call-points, inputs, outputs, and so on)
Yes
40,000
40,000
Video Cameras
Yes
128
128
 
 
 
 
FEP and Client Stations
Station Type
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Client Station
Yes, with Comark Monitor Card supervision
- Client
- FEP
- FEP, used as client and equipped with the Comark Monitor Card
 
 
 
 
Client Profiles
Station Type
Client Profile
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
UL 864/ULC S527-compliant fire station running on a UL 864/ULC S527-approved computer
A Client Profile (and the associated Scheme) defines Summary bar lamps, Event List, Event Detail bar, and alarm handling aspect and behavior.
Yes
- FS_UL
- FS_UL_SIMPLE
- FS_ULC
- FS_ULC_SIMPLE
- TBS_UL
- TBS_ULC
- BA_NA
- KIOSK
- FS_UL
- FS_UL_SIMPLE
- FS_ULC
- FS_ULC_SIMPLE
- TBS_UL
- TBS_ULC
UL 864/ULC S527-compliant fire station running on a UL 864/ULC S527-approved computer
Ability for Desigo CC to use project template including multiple client profiles
No
- template_DMS_AT
- template_Fire_EN
- template_Fire_DE
- template_Fire_UL
- template_Fire_ULC
- template_Fire_UL
- template_Fire_ULC
 
NOTE: For UL and ULC applications, verify that the language selected in Desigo CC is the same as the language selected on the Fire Alarm panels connected to it.
 
 
 
 
 
Event Disciplines Allowed in UL 864-/ULC S527-related Client Profiles
Client Profiles
Disciplines
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
FS_UL
FS_UL_SIMPLE
FS_ULC
FS_ULC_SIMPLE
(fire only)
- Building Automation
- Building Infrastructure
- Energy Management
- Remote Notification Messages
No
- Disciplines available
- Disciplines not available
- Disciplines not available
TBS_UL
TBS_ULC
- Building Automation
- Building Infrastructure
- Energy Management
No
- Disciplines available
- Disciplines available on non-fire stations
- Disciplines not available
- Disciplines available on non-fire stations
 
 
 
 
One-click treatment of events from Event List
Function
Permitted in UL 864? (Y/N)
Possible Settings
Settings Permitted in UL 864
Capability to command an event (Silence/Unsilence, Ack, Reset) from Event List without the need to select it first
Yes
- An event can be commanded without the need to select it first
- An event can be commanded only after it is selected
- An event can be commanded without the need to select it first (included in all UL compliant profiles)
 
 
 
 
Multiple Events Treatment Selection and Command
Function
Permitted in UL 864? (Y/N)
Possible Settings
Settings Permitted in UL 864
Multiple events treatment selection and command (Silence/Unsilence, Ack, Reset)
No
- Single event selection
- Multiple event selection
- Single event selection (included in all UL compliant profiles)
 
 
 
 
Audible Alert Buzzer
Function
Permitted in
UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Disabling Audible Alert Buzzer
No
Desigo CC has the capacity of permanently silence the Audible Alert Buzzer
Not allowed
(included in all UL/ULC compliant profiles)
 
 
 
 
Building Automation Events Priority on UL 864/ULC S527 Stations
System Type
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
UL 864/ULC S527-compliant systems handling building automation events (for example Alarms) at higher priority than fire events in the Supervisory and Trouble categories.
No, unless permitted by the Authority Having Jurisdiction.
Building Automation (BA) events can be mapped on different event categories using BACnet Notification Classes. By default, certain BA events have higher priority than Supervisory and Trouble events.
If required by Authority Having Jurisdiction, modify the Notification Class of BA events. We recommend using a BACnet event priority between 192 and 255 (Status category) for the To-Fault and To-Offnormal notifications.
 
 
 
 
Block Commands Programming
Block Command
NFPA 72 Configuration
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Block acknowledge
Local Highrise
Yes
- Enabled
- Not Enabled
- Enabled
Local Campus
No
- Enabled
- Not Enabled
- Not Enabled
Proprietary
No
- Enabled
- Not Enabled
- Not Enabled
 
 
 
 
Hard Disk Device Supervision
Function
Permitted in
UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Hard disk on system stations (Server, Client, and FEP stations)
Yes, if supervised
- Supervised hard disk drive (configured as a station device)
- Non-supervised hard disk drive (not configured as a workstation device)
- Supervised hard disk drive (configured as a station device)
 
 
 
Journaling Printout on UL 864/ULC S527-compliant Systems
UL 864/ULC S527-compliant fire systems must provide a journaling line printer that meets the related performance requirements of printing 50 event-related registrations in 90 seconds.
You must modify your printer’s default settings and select a pre-defined UL/ULC journaling template to ensure the printer meets the UL 864/ULC S527 requirements.
NOTE:
The printer settings shown in the following specification sections refer to the line printer model EPSON LQ-2090.
UL Journaling Template Specifications
The UL Template is a file named JournalingTemplate_UL.xml located at:
[installation drive:]\[installation folder]\[project]\profiles\JournalingUserTemplates.
You should use the UL template along with the line printer settings to ensure the required performance (50 Alarm-related events printed in 90 seconds). The UL Template has a condensed layout which results in a faster printout.
The following table provides configurations specifications for a journaling UL Template:
Configuration Setting for a Journaling UL Template.
Program Feature
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Journaling Template
Yes
Instead of Settings, select one of the following templates:
Default Journaling Template (standard layout)
UL Journaling Template (optimized layout)
UL Standard Fanfold Journaling Template (fanfold format 11x14 inches.)
The Default Template contains many columns while the UL Journaling Template contains an optimized layout with only four columns:
Transition Time
Current State
Event Source
Event Source Path
No separator line
UL Journaling Line Printer Specifications
To print the journaling data of 50 Alarm-related events in 90 seconds (for UL 864 requirements), you may need modify the default and control panel settings for the configured journaling line printer (server printer). The line printer model EPSON LQ-2090 was tested and the default settings and control panel settings were modified to be UL 864 compliant as follows:
Journaling Line Printer Specifications.
Program feature
Permitted in UL 864/ULC S527 ? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Line Printer Settings
Yes
Configurable settings:
Default settings mode
Control panel
Default settings mode:
Page length for front tractor: 11 inch
Page length for rear tractor: 11 inch
Skip over perforation: Off
Auto tear off: Off
Auto line feed: Off
Print Direction: Bi–D
Software: ESC/P 2
0 slash: 0
I/F mode: Auto
Auto I/F wait time: 10 seconds
Parallel I/F bidirectional mode: On
Packet mode: Auto
Auto CR (IBM PPDS): Off
A.G.M (IBM PPDS): Off
Character table: PC 437
International character set for Italic table: Italic U.S.A.
Font: Roman T
Manual Feed wait time: 1.5 seconds
Buzzer: On
Roll paper: Off
Low-noise mode: Off
Settings permitted in the line printer’s control panel:
Font select: HSD
Pitch select: 10cpi
CAUTION
Ensure that you have set the values for all available parameters for the line printer model that you have configured for the journaling printer. Failing to do so may result in the printer not satisfying the UL requirement.
To change your printer’s default settings, refer to the product-specific documentation.
 
 
 
 
Remote Notification (RENO) Functionality
Function
Permitted in
UL 2572? (Y/N)
Possible Settings
Settings Permitted in UL 2572
Remote Notification (RENO) Messages
No
- Used
- Not used
- Remote Notification (RENO) Messages shall not be used for UL 2572 Distributed Recipient Mass Notification Applications
 
 
 
 
Mass Notification Functionality
Function
Permitted in
UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Mass Notification Extension Module
No
- Installed
- Not installed
- MNS EM must be installed on a separate workstation with a dedicated client profile (FEP) and dedicated display. MNS events must not be displayed on the same monitor where Fire events are displayed
 
 
 
 
Mass Notification Devices
Function
Permitted in
UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Wireless/Mobile Devices in Mass Notification applications or similar
No
- Used
- Not used
- Not used
 
 
 
 
MNS and Voice Control Capability
Function
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
MNS and Voice control capability
No
Desigo CC can provide control to MNS and Voice functionality in conjunction with an XLS panel with MNS event types.
For MNS and Voice control capability, Desigo CC must have the panel associated with it in the same room and adjacent (in close proximity) to the computer with the intent that a single person can operate both units.
 
 
 
 
MNS Remote Notification Support
Function
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
MNS remote notification support
No
Ability to support MNS notification via pagers, SMS, or similar media.
Not Allowed.
Not verified by UL.
 
 
 
 
 
 
Virtual Machines Support
Function
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Support for multiple Virtual Machine applications in Desigo CC.
No
One or multiple Virtual Machines are supported in Desigo CC.
Virtual Machine application is limited to one application per computer.
 
 
 
 
Backup Computer Capabilities Support in Virtual Machines
Function
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Backup computer capabilities support in Desigo CC with Virtual Machine application.
No
Desigo CC with Virtual Machine application allows the support of backup computer capabilities.
Not Allowed
 
 
 
 
Bandwidth Capability
Function
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Bandwidth capability
No
Desigo CC can support up to 100 Mbps network bandwidth capability.
Total network bandwidth (including video and others) must not exceed 50 Mbps.
Bandwidth used for other applications, such as video and others, must not exceed 45 Mbps.
In addition, the maximum bandwidth must be measured and recorded prior to commissioning the system.
 
 
 
 
Remote Desktop Application
Function
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Support for Remote Desktop application
No
Ability to remotely connect to Desigo CC in Engineering (diagnostics) and Operating mode
Remote Desktop is allowed for Engineering mode only
 
 
 
 
Distributed System
Function
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Distributed System
Only with UL-listed network switch units
Ability to use Ethernet switch units that are not UL-listed
For Distributed System topology, UL864-listed Ethernet switch units must be used.
 
 
 
 
Mobile and Windows App
Function
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Mobile and Windows App
Read-only
Mobile and Windows App configured for:
Read-only
Event control
Read-only
 
 
 
 
 
Management Station with Fire Control
Function
Permitted in UL 864/ULC S527? (Y/N)
Possible Settings
Settings Permitted in UL 864/ULC S527
Management Station with Fire control configured for Manned and Unmanned operations
Manned-only
Manned operations
Unmanned operations
Manned operations